Translate

THANKS

Thanks for being touch with us on Social media and online website

×
Thanks!
for visiting the electricaldon.com website.Received many applications for ITI ELECTRICIAN for job. Kindly note our team is working on it, shortly you will receive call from them.

APPLY only if you have Electrical wiremen or Electrical Supervisor Licenses its Mandatory. !

Thankyou for your Patients. !

Search This Blog

9681 main transformer backup protection relay

 
The 9681 main transformers High-Voltage side backup protection relay is applicable to the protection of the three-winding main transformer high voltage side backup protection and two winding main transformer high voltage side backup protection, Such protection is generally the concentrated the screen, it can also be installed separated, Fully supported the distributed protection system.
the protection device consists of the completed two or three winding main transformer protection with the 9692,9693 main transformer differential protection device, the 982 main transformer medium-voltage side backup  protection measuring and control device, the 9683 main transformers low Voltage side backup protection measuring and control device, the 984 main transformer backup operating gear, the 985 main transformers non-electric quantity protection,
 the function of the protection relay 
   Overcurrent instantaneous trip(trip segmentation), with low voltage lockout, negative sequence voltage lockout.
    time delay overcurrent instantaneous trip(all the breakers in the main transformer trip), with low voltage lockout, negative sequence voltage lockout.
    The Over-current instantaneous trip and time delay overcurrent instantaneous trip can be chosen, interphase direction selection.
     time delay current instantaneous trip (time delay current instantaneous trip, the direction of the time delay the current instantaneous trip, low voltage lockout);
     overload alarm.
    CT line-break
     zero sequences over current(zero sequence overcurrent, Zero sequence voltage lockout、zero sequence trip、Zero sequence direction selection).
   Clearance zero sequence protection,
     PT no voltage(alarm),
    PT line-break(alarm),
     busbar grounding  (alarm),
     pressure anomaly  (SF6 Low-pressure alarm),
 
Measuring and control
     busbar voltage  :Uab、Ubc、Uca;Ua、Ub、Uc;
     measuring current  :Ia、 Ib、 Ic、
    power:P、Q、cosФ;
    frequency:f;
 
Auxiliary function
   control circuit break,
    Manual closing and switch in
    remote closing and switch in.
    Fault recorder
 
 communication mode 
    485 communication
    Ethernet communication
    Optical fiber communication.
  Protective action principle
①  time delay  current instantaneous trip protection
    1.RLP1  time delay  current instantaneous trip protection-in  service
    2.Protective current IA(IB)IC anyone sampling value≧ the fixed value of the time delay current instantaneous trip protection(Idz3)
    3.Time of the current≧time delay current instantaneous trip protection tzd3
    Protect immediate  output C7/C8、C9/C10、C11/C12, at the same time the 同时驱动accident signal relay drive C1/C3(return after 10s ), Panel accident light
 
②  I—II segment Combined voltage blocking over current protection
The device is set with a three-segment composite voltage blocking over current protection. Three-section protection and time setting value can be set separately, According to the actual situation, we can choose the compound voltage or the compound voltage to start over current protection. In order to prevent the decrease of the PT line-break or the PT  voltage, the protection will automatically withdraw from the negative sequence voltage and low voltage when the alarm signal occurs.
 (1).Zero sequence current instantaneous trip protection    (Delayed time trip  C15/C16)
    (2).Zero sequence time delay  current instantaneous trip   (Delayed jump trip the sideC7/C8)
    (3).Zero-Sequence definite time over-current    (Delayed trip, trip to the side, the side of the trip C7/C8、C9/C10、C11/C12)
    (4).Low voltage blocking over current;    (Need to put "over current" protection at the same time,and no  PT line-break, no PT loss voltage)
the low voltage judge by Uca Line voltage, the current is greater than the set value at a certain phase, Uca line voltage is less than the set value(General low voltage set value is 70V), then protection will be able to move,It is mainly used for the discrimination of voltage symmetrical short circuit, and the negative sequence voltage;
    (5).Negative sequence voltage lockout over-current; (need and put into "over current protection and a continuous line of PT without losing pressure) negative sequence voltage is mainly used for voltage asymmetric short circuit, in a phase, current protection is greater than the set value, the negative sequence voltage greater than a set value (usually negative sequence voltage setting for 7V) protection will be an act.
Description: at the same time put into the "over current, low voltage blocking over current, negative sequence voltage blocking off flow", can reduce the current transient error, and can guarantee the voltage in the symmetrical short circuit and asymmetric short circuit protection action.
 
③  Clearance zero sequence overcurrent protection
    1.RLP12 Clearance zero sequence-in service
    2.Gap zero-sequence current Io sampling value ≧Clearance over current fixed value(Ijdz1)
    3.Time of Zero sequences current ≧Clearance overcurrent delay tjzd1
    Protect immediate exit C7/C8、C9/C10、C11/C12,Simultaneous drive accident signal relay C1/C3(Return after 10s), Panel accident light.
 
④  Overload
    1.RLP9  Over load-in service;
    2.Protection current IA(IB)IC anyone sampling value≧ Overload  fixed value(Idz4)
    3.Time of current≧Overload delay tzd4
   Protection immediately driving alarm signal relay C2/C3(return after 10s). Panel warning light.
Description: if overload needs on-load voltage regulation (the low backup is open the fan overload, the same as following), you need to
Description: overload if you need to lock the load voltage adjustment (low backup is overload open the fan, with the next), you need to
1.RLP17  Overload alarm -in service
    2.RLP18   Overload on- load voltage regulation-in service
    3.Protection current IA(IB)IC Any phase sampling value≧ Overload fixed value(Idz4)
    4.Time of current≧Overload delay tzd4
  Protect immediate exitC17/C18,Simultaneous drive accident signal relay C1/C3(Return after 10s). The panel warning light is on.
 
⑤ Zero sequence overcurrent
    1.RLP8  Zero sequence overcurrent-in service
    2.Zero sequence current 3Io sampling value≧ Zero sequence overcurrent fixed value(Iodz)
    3.After a period of delay(Exit C15/C16)、The two section(export C7/C8、C9/C10、C11/C12)、 three-section  (Exit C7/C8、C9/C10、C11/C12)
    Protection immediate exit, while driving accident signal relay C1/C3(Return after 10s). Panel accident light. 
⑥  Zero sequence over-voltage
    1.RLP11  Zero sequence over-voltage-in service
    2.Zero sequence voltage 3Uo sampling value  ≧ Zero sequence overvoltage(Uodz2)
    3.After delay T0zd4 
    Protect immediate exit C7/C8、C9/C10、C11/C12,Simultaneous drive accident signal relay C1/C3(Return after 10s). Panel accident light
 
⑦  control circuit break
  1.RLP7  control circuit break-in service
    2.Protection device control circuit break time≧Control loop delay(Tdz3);
    Protection immediately driving alarm signal relay C2/C3(Return after 10s). Panel warning light
    Description: the control loop is broken.:
   If the switch is in the position of the closing status, the information of the control loop is broken, the trip coil circuit is disconnected.;
   If the switch in a state of breaking, send out the "control loop break" information, then the closing coil circuit disconnect 














No comments:

Transformer Fittings And Accessories

  Oil conservator with drain plug and oil filling hole Oil level indicator Drain valve with plug Filter valve with plug Air release vent Exp...